Item | Technical Index | Specification |
Technical Specifications | Input voltage | Single / three-phase 200-240V, three-phase 380-440V. The fluctuation does not exceed ±10% , and the unbalance rate is less than 3% |
Input frequency | 50/60Hz ±5% | |
Output voltage | 0V-input voltage | |
Output frequency | 0-3200Hz | |
Performance | Programmable input and output terminals | Input terminal function can be edited, output terminal function can be edited |
Process PID adjustment function | Built-in process PID module | |
Simple PLC function | Built-in simple PLC module, which can realize timing and multi-segment frequency output | |
Textile swing frequency function | Built-in textile swing frequency function module | |
Fixed length control function Protocol | Built-in fixed-length control module. Standard MODBUS communication protocol. | |
Protective function | Overvoltage stall | Automatic bus voltage control to prevent overvoltage faults caused by large inertia load deceleration and power generation |
Automatic current limiting protection | The output current is automatically limited to prevent heavy load overcurrent faults, and the heavy load has the overcurrent speed limiting performance of the excavator | |
Input and output phase loss protection | Output phase loss automatic detection and alarm function | |
Process PID given, feedback loss detection | Process PID automatically recognizes whether the given and feedback are lost, and the loss of alarm function | |
Output short-circuit protection to ground | Effective protection function of output short circuit to ground | |
Output phase-to-phase short-circuit protection | Output phase-to-phase short circuit effective protection function | |
Module overheating protection | When the load is too heavy, the fan is damaged or the cooling air duct is blocked, real-time monitoring of the module temperature and hot spot protection | |
Fan follow-up start with temperature control | The fan only rotates when the inverter is running, and the fan will stop after a delay when the temperature is too high when the inverter is stopped. | |
Input & Output | External analog power supply | +10V, load capacity 100mA, used for external analog power supply, with short circuit protection |
External digital power supply | +24V, load capacity 200mA | |
Analog input | AI1 : Voltage 0-10V and 0-20mA input can be set by software menu to select input mode | |
Analog output | AOV: 0-10V, AOI: 0-20mA , 4~20mA output can be realized through parameter setting | |
Digital input | DI1-DI5,DI5can be selected as high-speed pulse signal, 0~50KHz | |
Digital output | FM digital output, also high-speed pulse output, 0~50KHz | |
Relay output | TA/TB/TC : Contact capacity 250VAC/3A or 30VDC/1A (with timing relay on-off setting function ) | |
MODBUS-RTU communication | A+ and B- interfaces are suitable for the international standard MODBUS-RTU protocol format | |
External expansion keyboard (optional) | The RJ45 interface can connect an external expansion keyboard, and the external keyboard can adjust the speed to start monitoring or control parameters | |
Operation display | LED display | 5-digit LED digital tube Setting frequency, output frequency, output voltage, output current, motor speed, output torque, switch terminals, status parameters, programming menu parameters and fault codes, etc. |
Indicator light | 3unit lights,3status lights | |
Environmental characteristics | Working temperature | -10~+40℃, maximum 50℃, air temperature change less than 0.5℃/min |
40~50℃ need to be derated: the output current is derated by 2% every time it exceeds1℃ | ||
Storage ambient temperature | -40~+70℃ | |
Place of use Altitude | Indoor, no direct sunlight, no dust, corrosive gas, flammable gas, oil mist, water vapor, dripping water or salt, etc. Below 1000 meters, derating is required for use above 1000 meters, derating is 1% for every 100 meters above 1000 meters, and the maximum altitude is 3000 meters | |
Humidity | Less than 95%RH , no condensation | |
Vibration resistance | 3.5m/s 2 at 2-9Hz , 10m/s 2 at 9-200Hz (IEC60721-3-3) | |
Protection class | IP20 | |
Pollution level | Class 2 (dry, non-conductive dust pollution) |
No. | Items | FC100E |
1 | Reliable hardware | Only first-class components are built-in. |
2 | Robust design | All the components are selected at higher size. |
3 | PCB aging test | 100% test, 45°C, 12 hours. |
4 | Finished products aging test | 100% test, 50°C, 24 hours. |
5 | Loading test | Two times, 100%: |
6 | Grouped pulse testing | Without failure under 4500V (better EMC performance). |
7 | Electrostatic testing | 1. Noncontact conditions -- without failure under 10000V. |
8 | Unqualified during production | <0.03% |
9 | Total failure ratio at industrial sites | <0.5% |
10 | High overload capacity | 150% / 60s, 180% / 10s, 200% /1s |
11 | Smart start / stop mode | Acceleration / Deceleration time can be set as 0.0s, the inverter start and stop the motor as fast as possible without failure. |
12 | S curve Acceleration / Deceleration mode | Better start stop performance. |
13 | Big start torque | 0.5Hz/150% |
14 | Better stop performance | 1. Current is limited smoothly while stopping; |
15 | Better input voltage flexibility | -15%~+15% without failure. |
16 | RS485 communication | Easy to use; Independent terminal wiring, and keyboard can be used at the same time |
Inverter Model | Motor | Rated Input Current (A) | Rated Output Current (A) | |
kW | HP | |||
1AC 220~240V±15% | ||||
FC100E-2S-0.4G | 0.4 | 0.5 | 6.5 | 2.1 |
FC100E-2S-0.75G | 0.75 | 1 | 8.2 | 4 |
FC100E-2S-1.5G | 1.5 | 2 | 14 | 7 |
FC100E-2S-2.2G | 2.2 | 3 | 23 | 9.6 |
FC100E-2S-4.0G | 4.0 | 5 | 40 | 16.5 |
FC100E-2S-5.5G | 5.5 | 7 | 55 | 20 |
FC100E-2S-7.5G | 7.5 | 10 | 70 | 30 |
3AC 380~460V±15% | ||||
FC100E-4T-0.75G | 0.75 | 1 | 3.4 | 2.1 |
FC100E-4T-1.5G | 1.5 | 2 | 5.0 | 3.8 |
FC100E-4T-2.2G | 2.2 | 3 | 5.8 | 5.1 |
FC100E-4T-4.0G | 4.0 | 5 | 10.5 | 9 |
FC100E-4T-5.5G | 5.5 | 7 | 14.6 | 13 |
FC100E-4T-7.5G | 7.5 | 10 | 19 | 17 |
FC100E-4T-11G | 11 | 15 | 28 | 25 |
FC100E-4T-15G | 15 | 20 | 35 | 32 |