Availability: | |
---|---|
Quantity: | |
Product Feature
1. Ultra-low noise design, the sound of the motor running is soft and pleasant
2. IP54 high protection design, dustproof and waterproof
3. Convenient parameter setting, one-key macro parameter setting online function
4. Complete protection functions
Product Selection
Item No. | Adaptable Motor (kW) | Input Current (A) | Output Current (A) | Rate Capacity (kVA) | W (mm) | H (mm) | D (mm) | W1 (mm) | H1 (mm) | Diameter (mm) | GW (kg) |
3 Phase Input and 3 Phase Output 380V (-15%~+15% Tolerance) | |||||||||||
FC610-4T-2.2P | 2.2 | 5.8 | 5.1 | 4 | 126 | 173 | 136 | 101 | 158 | Ø3.5 | 2.48 |
FC610-4T-4.0P | 4 | 10 | 8.6 | 5.9 | 126 | 173 | 136 | 101 | 158 | Ø3.5 | 2.48 |
FC610-4T-5.5P | 5.5 | 14.6 | 12.5 | 8.6 | 200 | 235 | 146 | 129 | 225 | Ø4 | 3.85 |
FC610-4T-7.5P | 7.5 | 20.5 | 17.5 | 12 | 200 | 235 | 146 | 129 | 225 | Ø4 | 3.85 |
FC610-4T-11P | 11 | 28 | 25 | 16 | 200 | 235 | 146 | 129 | 225 | Ø4 | 4 |
1 Phase Input and 3 Phase Output 220V (-15%~+15% Tolerance) | |||||||||||
FC610-2S-0.75P | 0.75 | 8.2 | 4 | 1.5 | 126 | 173 | 136 | 101 | 158 | Ø3.5 | 2.48 |
FC610-2S-1.5P | 1.5 | 14 | 7 | 3 | 126 | 173 | 136 | 101 | 158 | Ø3.5 | 2.48 |
FC610-2S-2.2P | 2.2 | 23 | 9.6 | 4 | 126 | 173 | 136 | 101 | 158 | Ø3.5 | 2.48 |
Technical Parameter
Electrical Specification | |
Input Voltage | Single Phase/Three Phase 200-240V, Three Phase 380-440V |
Fluctuate no more than±10%,Imbalance Rate <3% | |
Input Frequency | 50/60Hz ± 5% |
Output Voltage | 0V-Input Voltage |
10~60Hz | |
Performance | |
Overload Capacity | 110% rated output current for 1 minute |
Control Method | V/F Control |
Run Command Setting Method | Operation panel setting, analog setting, communication setting |
Speed Setting Method | Digital setting, analog setting/pulse setting, communication setting |
Protective function | |
Overvoltage Stall | Bus voltage automatic control to prevent overvoltage fault |
Automatic Current Limiting Protection | Output current is automatically limited to prevent over-current faults |
Overload Pre-Alarm & Alarm | Overload Pre-warning and protection |
Output Phase Loss Protection | Output phase loss automatic detection and alarm function |
Overvoltage & Overflow Stall Control | Automatically limit current and voltage during operation to prevent frequent over-current and over-voltage tripping |
Output Short-to-Ground Protection | Effective protection function for output short circuit to ground |
Output Phase-to-Phase Short Circuit Protection | Output interphase short circuit effective protection function |
Input & Output | |
External analog power supply | +24V,load capacity 100mA |
Analog Input | AI1:Voltage 0-10V/0-20mA |
AI2:Voltage 0-10V/0-20mA | |
Digital Input | DI1、DI2 |
Digital Output | DO1 |
Relay output | TA/TB/TC:Contact rating 250VAC/3A Or 30VDC/1A |
MUDBUS Communication | A+、B- |
Operation Display | |
LED Display | 4 digit LED digital tube |
Output frequency, output current, current pressure, set pressure and fault code etc. | |
Indicator Light | 4 status lights |
Environmental characteristics | |
Working Temperature | -10-+40℃, Maximum temperature is 50°C, Air Temperature change is less than 0.5°C/min,40-50℃ Derating is required, output current derating 2% for each 1℃ |
Storage Environment Temperature | -40-+70℃ |
Altitude | Less than 1000 meters, derating is required for more than 1000 meters |
Humidity | Less than 95%RH, no condensation |
Vibration resistance | 3.5m/s² at 2-9Hz, 10m/s² at 9-200Hz (IEC60721-3-3) |
Protection Degree | IP54 |
Pollution Level | Class 2 (dry, non-conductive dust pollution) |